• Click on Header Row to go to Codes Websites [Have you bought your code copies?]
  • Updated August 2026
  • ©2026 Safer Buildings Coalition

Show columns
TOPIC IFC 2015 IFC 2018 IFC 2021 IFC 2024 IFC 2027 – COMING SOON
Relevant Referenced Standards – IFC Ch. 80 NFPA 72-2013 NFPA 72-2016
NFPA 1221-2016
NFPA 72-2019
NFPA 1221-2019
NFPA 72-2022
NFPA 1225-2022
Approved Emergency Services Department Communications Required Sec. 510.1, 510.2 Sec. 510.1, 510.2 Sec. 510.1, 510.2 Sec. 510.1 , 510.2
Note: Exception 4
One Story Buildings less than 12,000 Sq. Ft.
Field testing – Building Signal Coverage Assessment Required 510.6.3 510.6.4 510.6.4 510.6.4
Permit Required Section 510.3 Section 510.3 Section 510.3 Section 510.3
Listing of Equipment Not Specifically Addressed in Section 510 Not Specifically Addressed in Section 510 Sec. 510.4 – Listed to UL 2524 Sec. 510.4 – Listed to UL 2524
Limitation of External References Not specifically addressed Not specifically addressed Not specifically addressed Not specifically addressed
Signal Strength and Quality &
Area Coverage Required
-95 dBm Sec. 510.4.1.1 & 510.4.1.2
95% General – Sec. 510.4.1
99% Critical – Not Specifically Addressed in Sec. 510
DAQ 3.0 Sec. 510.4.1.1
95% General – Sec. 510.4.1
99% Critical – Not Specifically Addressed in Sec. 510
-95 dBm & DAQ 3.0 Sec. 510.4.1.1
95% General – Sec. 510.4.1
99% Critical – Sec. 510.4.1
DAQ 3.0 Sec. 510.4.1.1
95% General – Sec. 510.4.1
99% Critical – Sec. 510.4.1
IFC reference to NFPA 1221 or 1225 Standards No Sec. 510.4.2 & 510.5 Reference to NFPA 1221-2016 Sec. 510.4.2 & 510.5 Reference to NFPA 1221-2019 Sec. 510.4.2 & 510.5 Reference to NFPA 1225-2022
Backbone / Riser Cable Defined Not Defined Not Defined Refers to NFPA 1221-2019 Refers to NFPA 1225-2022
Distribution / Feeder Cable Defined Not Defined Not Defined Refers to NFPA 1221-2019 Refers to NFPA 1225-2022
Pathway Survivability: Fire Rating Not Specifically Addressed in Section 510.
Referenced in 2013 NFPA 72 Section 24.3.6.8
Where Required in NFPA 1221-2016
Note: Also See NFPA 1221 TIA 16-2
Where Required in NFPA 1221-2019 Where Required in NFPA 1225-2022
Pathway Survivability: Mechanical Protection Not Specifically Addressed in Section 510.
Referenced in 2013 NFPA 72 Section 24.3.6.8
Where Required in NFPA 1221-2016 Where Required in NFPA 1221-2019 Where Required in NFPA 1225-2022
Plenum Rated Coaxial Cable Required Not Specifically Addressed in Section 510.
Referenced in 2013 NFPA 72 Section 24.3.6.8
Where Required in NFPA 1221-2016 Where Required in NFPA 1221-2019 Where Required in NFPA 1225-2022
Lightning Protection Required Not Specifically Addressed in Section 510 Where Required in NFPA 1221-2016 Where Required in NFPA 1221-2019 Where Required in NFPA 1225-2022
Noise Floor Requirement Not Specifically Addressed in Section 510 Not Specifically Addressed in Section 510 Not Specifically Addressed in Section 510 Sec. 510.4.2.9
Also see NFPA 1225-2022 Sec. 18.9.3
Technical Criteria to be Provided by AHJ(s) 510.4.2.2 510.4.2.2 510.4.2.2 510.4.2.2
Standby Power 24 Hours – Sec. 510.4.2.3 12 Hours – Sec. 510.4.2.3 or
2-Hours Battery w/ Emergency Generator
12 Hours – Sec. 510.4.2.3 or
2-Hours Battery w/ Emergency Generator
12 Hours – Sec. 510.4.2.3 or
2-Hours Battery w/ Emergency Generator
Isolation of Donor Antenna Required Not Specifically Addressed in Sec. 510 20db – Sec. 510.4.2.4(4) 20 db Above System Gain – Sec. 510.4.2.4(4) 20 db Above System Gain – Sec. 510.4.2.4(4)
Cabinets for Equipment and Battery Backup Required NEMA 4 – Sec. 510.4.2.4 (1) & (2) NEMA 4/NEMA 3R – Sec. 510.4.2.4 (1) & (2) NEMA 4/NEMA 3R – Sec. 510.4.2.4 (1) & (2) NEMA 4/NEMA 3R – Sec. 510.4.2.4 (1) & (2)
Frequency License Holder Approval Required Yes under FCC Part 90.219 Referenced in Sec. 510.4 Yes under FCC Part 90.219 Referenced in Sec. 510.4 Yes under FCC Part 90.219 Referenced in Sec. 510.5 Yes – Fire Code Official & Frequency License Holder
Sec. 510.5.2 & 510.5.2.1
FCC Part 90.219 – Sec. 510.5.5
Oscillation Prevention 510.5.3 510.4.2.4 510.4.2.4 510.4.2.4
Monitoring By Fire Alarm Required 510.4.2.4 Yes – Sec. 510.4.2.5 Yes – Sec. 510.4.2.5 Yes – Sec. 510.4.2.5
Monitor Signal Source Malfunction Required Not Specifically Addressed in Section 510 Donor Antenna – Sec. 510.4.2.5 Donor Antenna – Sec. 510.4.2.5 Signal Source – Sec. 510.4.2.5
Dedicated Annunciation Required Where approved by Fire Code Official: 510.4.2.4 Where approved by Fire Code Official: 510.4.2.5 Where approved by Fire Code Official: 510.4.2.5 Where approved by Fire Code Official: 510.4.2.5
Additional Frequencies (May Include cellular and new technologies) Sec. 510.6.2 Additional Frequencies Made Available by FCC Sec. 510.6.2 Additional Frequencies Made Available by FCC Sec. 510.6.2 Additional Frequencies Made Available by FCC Sec. 510.4.2.6 & 510.6.2
Also see NFPA 1225-2022 A.3.3.63
Design Documents Not Specifically Addressed in Section 510 510.4.2.7 510.4.2.7 510.4.2.7
Communication Antenna Density/Near Far Not Specifically Addressed in Section 510 Sec. 510.4.2.8 Sec. 510.4.2.8 Sec. 510.4.2.8
Mounting of Donor Antenna Not Specifically Addressed in Section 510 Not Specifically Addressed in Section 510 Sec. 510.5.1 Sec. 510.5.1
Approval prior to installation 510.5.1 510.5.1 510.5.2 510.5.2
Minimum qualifications of personnel 510.5.2 510.5.2 510.5.3 510.5.3
System Testing – Initial, Acceptance, Annual, 5-year New/Acceptance, Sec. 510.5.3
Annual Sec 510.6.1
New/Acceptance, Sec. 510.5.3
Annual Sec 510.6.1
New Systems Sec. 510.5.4
Annual – Section 510.6.1
New Systems Sec. 510.5.4
Annual – Section 510.6.1
Compliance with FCC Part 90.219 Sec. 510.5.4 Sec. 510.5.4 Sec. 510.5.5 Sec. 510.5.5
Responsibility to Prevent or Correct Interference with Public Safety System By reference: 510.5.4 FCC compliance By reference: 510.5.4 FCC compliance By reference: 510.5.5 FCC compliance By reference: 510.5.5 FCC compliance
Nonpublic safety system – non-interference Not Specifically Addressed in Section 510 510.6.3 510.6.3 510.6.3